Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 146

60 hz.
Hide thumbs
SiUS34-907
Measure the inverter output voltage
(*2).
Power OFF
Note: Measurement should be made
while the frequency is stable.
output voltage between 3
Power ON
*1: Pressure difference between high pressure and low pressure before starting.
*2: The quality of power transistors / diode modules can be judged by executing
Troubleshooting
A
Check
if the inverter
NO
phases is within
± 5V.
YES
Troubleshooting by Indication on the Remote Controller
Replace the inverter PCB.
Replace the inverter
compressor.
(P.213).