Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 178

60 hz.
Hide thumbs
SiUS34-907
P1
3.34 "
" High Voltage of Capacitor in Main Inverter Circuit
P1
Remote
Controller
Display
Applicable
RXYMQ36 · 48PVJU
Models
Method of
Imbalance in supply voltage is detected in PCB.
Malfunction
Detection
Malfunction
When the imbalance in the power supply voltage becomes more than 6V
The unit operation is continued without malfunction decision.
Decision
P1
"
Conditions
 Open phase
Supposed
 Voltage imbalance between phases
Causes
 Defect of main circuit capacitor
 Defect of main PCB
 Improper main circuit wiring
Troubleshooting
" will be displayed by pressing the inspection button.
Troubleshooting by Indication on the Remote Controller