60 hz.
Hide thumbs
SiUS34-907
L4
3.30 "
" Malfunction of Inverter Radiation Fin Temperature
Rise
L4
Remote
Controller
Display
Applicable
RXYMQ36 · 48PVJU
Models
Method of
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Detection
Malfunction
When the temperature of the inverter radiation fin increases above 181°F
Decision
Conditions
 Actuation of fin thermal (Actuates above 181°F)
Supposed
 Defect of main PCB
Causes
 Defect of fin thermistor
Troubleshooting
Troubleshooting by Indication on the Remote Controller