Daikin VRV III-S RXYMQ36 48PVJU Service Manual page 20

R-410a heat pump 60hz
Table of Contents

Advertisement

SiUS34-907
Slim Ceiling Mounted Duct Type
Model
1 Cooling Capacity
2 Heating Capacity
Casing / Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output
Fan
Airflow Rate (H/L)
External Static Pressure
4
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB (27°CDB), 67°FWB (19.4°CWB)
Outdoor temperature: 95°FDB (35°CDB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°CDB).
Outdoor temperature: 47°FDB (8.3°CDB), 43°FWB (6°FWB)
Equivalent ref. piping length: 25ft (7.5 m) (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure means
"High static pressure – Standard – Low static pressure".
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Specifications
FXDQ18MVJU
Btu/h
Btu/h
Galvanized Steel Plate
in. (mm)
7-7/8 × 35-7/16 × 24-7/16 (200 x 900 x 621)
ft²(m²)
Sirocco Fan
kw
cfm
440/350 (H/L)
psi
0.0064-0.0022
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ1/4 (6.4) (Flare Connection)
in. (mm)
φ 1/2 (12.7) (Flare Connection)
in. (mm)
in. (mm)
(External Dia. 1-1/32 (26.2) Internal Dia. 25/32 (19.9))
Lbs (kg)
dBA
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Insulation for Fitting,
Sealing Pads, Clamps, Screws, Washers, Conduit Mounting
Plate, Insulation Tube.
18,000
20,000
3 × 12 × 17
1.89 (0.6)
0.13
VP20
63 (28.5)
35/31
Fuse,
C:3D051780A
FXDQ24MVJU
24,000
27,000
Galvanized Steel Plate
7-7/8 × 43-5/16 × 24-7/16 (200 x 1100 x 621)
3 × 12 × 17
2.44 (0.7)
Sirocco Fan
0.13
580/460 (H/L)
0.0064-0.0022
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ 3/8 (9.5) (Flare Connection)
φ5/8 (15.8) (Flare Connection)
VP20
(External Dia. 1-1/32 (26.2) Internal Dia. 25/32 (19.9))
71 (32)
36/32
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Insulation for Fitting,
Sealing Pads, Clamps, Screws, Washers, Conduit
Mounting Plate, Insulation Tube.
Specifications
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R-410aVrv iii-s rxymq36-48pvju