Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 221

60 hz.
Hide thumbs
CHECK 3
Check for Fan Motor Connector
(1) Turn the power supply off.
(2) With the fan motor connector disconnected, measure the resistance between each pin, then make sure that
the resistance is more than the value mentioned in the following table.
GND
212
1 White
2 Orange
3 Brown
4 Blue
5
6
7 Red
Measurement point
Judgement
1 - 4
1MΩ or more
2 - 4
100kΩ or more
3 - 4
100Ω or more
4 - 7
100kΩ or more
SiUS34-907
Troubleshooting