Field Setting
c. Monitor mode
To enter the monitor mode, push the
MODE (BS1) button when in
"Setting mode 1".
<Selection of setting item>
Push the SET (BS2) button and set
the LED display to a setting item.
<Confirmation on setting contents>
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
"Monitor mode".
∗ Push the MODE (BS1) button and
returns to "Setting mode 1".
80
No.
Setting item
0
Various setting
1
C/H unified address
2
Low noise/demand address
3
Not used
4
AIRNET address
5
Number of connected indoor units
Number of connected zone units
7
(excluding outdoor and BS unit)
8
Number of outdoor units
Number of zone units (excluding
11
outdoor and BS unit)
12
Number of terminal blocks
13
Number of terminal blocks
Contents of malfunction (the
14
latest)
Contents of malfunction
15
(1 cycle before)
Contents of malfunction
16
(2 cycle before)
20
Contents of retry (the latest)
21
Contents of retry (1 cycle before)
22
Contents of retry (2 cycle before)
Normal judgement of outdoor units
25
PCB
The numbers in the "No." column represent the number of times to press the SET
(BS2) button.
Setting item 0 Display contents of "Various setting"
EMG operation /
ON
backup operation
OFF
setting
Defrost select setting
Short
Medium
Long
Te setting
H
M
L
Tc setting
H
M
L
LED display
H1P H2P H3P H4P H5P H6P H7P
l h h h h h h
l h h h h h k
l h h h h k h
l h h h h k k
l h h h k h h
l h h h k h k
l h h h k k k
l h h k h h h
l h h k h k k
l h h k k h h
l h h k k h k
k h h k k k h
k h h k k k k
k h k h h h h
k h k h k h h
k h k h k h k
k h k h k k h
l h k k h h k
l h h k h h h
l h h h h h h
l h h h k h h
l h h h l h h
l h h h h h h
l h h h h k h
l h h h h l h
l h h h h h h
l h h h h h k
l h h h h h l
l h h h h h h
SiUS34-907
Data display
See below
Lower 6 digits
Lower 6 digits
Lower 4 digits: upper
Lower 4 digits: lower
Malfunction code table
Refer to P.103.
Lower 2 digits:
k h
Abnormal
h k
Normal
h h
Unjudgement
Test Operation