Page of 264
Download Table of ContentsContents Print This PagePrint Bookmark

Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 26

60 hz.
Hide thumbs
SiUS34-907
Wall Mounted Type
Model
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output
Airflow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB (27°CDB), 67°FWB (19.4°CWB)
Outdoor temperature: 95°FDB (35°CDB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°CDB).
Outdoor temperature: 47°FDB (8.3°CDB), 43°FWB (6°FWB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Specifications
FXAQ18MVJU
Btu/h
Btu/h
White (3.0Y8.5/0.5)
in. (mm)
11–3/8 × 41–3/8 × 9 (289 x 1051 x 229)
ft² (m²)
Cross Flow Fan
kw
cfm
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ 1/4 (6.4) (Flare Connection)
in. (mm)
φ 1/2 (12.7) (Flare Connection)
in. (mm)
in. (mm)
(External Dia. 11/16 (17.5) Internal Dia. 1/2 (12.7) )
Lbs (kg)
dBA
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual, Installation Panel,
Paper Pattern for Installation, Insulation Tube, Clamps,
Screws.
18,000
20,000
2×14×17
2.29 (0.7)
QCL9686
0.043
500/400
VP13
31(14)
43
Fuse
C:3D046038A
FXAQ24MVJU
24,000
27,000
White (3.0Y8.5/0.5)
11–3/8 × 41–3/8 × 9 (289 x 1051 x 229)
2×14×17
2.29 (0.7)
QCL9686
Cross Flow Fan
0.043
635/470
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ3/8 (9.5) (Flare Connection)
φ5/8 (15.8 (Flare Connection)
VP13
(External Dia. 11/16 (17.5) Internal Dia. 1/2 (12.7) )
31 (14)
47
Fuse
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual, Installation Panel,
Paper Pattern for Installation, Insulation Tube, Clamps,
Screws.
Specifications
17

   Related Manuals for Daikin VRV III-S RXYMQ36 48PVJU

This manual also for:

R-410a