Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 78

60 hz.
Hide thumbs
SiUS34-907
3.1.7 Centralized Control Group No. Setting
BRC1E Type
In order to conduct the centralized remote control using the centralized remote controller and the unified ON/OFF
controller, Group No. settings should be made by group using the operating remote controller.
Make Group No. settings for centralized remote control using the operating remote controller.
(1) <Basic screen>
(2) <Service Settings menu screen>
(3) <Group Address>
(3) <Group Address (Group)>
Notes:
 For wireless remote controller, see the following.
 For setting group No. of HRV and wiring adaptor for other air conditioners, refer to the instruction manual
attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to keep
the installation table with the operation manual for maintenance.
Test Operation
1.
Press and hold Cancel button for 4 seconds or more.
Service Settings menu in displayed.
Group Address
2.
Select
Group Address screen is displayed.
3.
Select Group Address (Group), and press Menu/OK button.
Group Address (Group) screen is displayed.
Select the group No. by using  (Up/Down) button.
4.
Press Menu/OK button.
, and press Menu/OK button.
Field Setting
69