60 hz.
Hide thumbs
SiUS34-907
Malfunction
code
Indoor Unit
A0
A1
A3
A6
A7
A9
AF
AJ
C4
C5
C9
CJ
Outdoor Unit
E1
E3
E4
E5
E6
E7
E9
F3
F6
H3
H4
H7
H9
J2
J3
J5
J6
J7
J9
JA
JC
L0
L1
L4
L5
L8
L9
LA
P1
P4
Troubleshooting
Operation
lamp
l
Error of External Protection Device
l
PCB Defect
l
Malfunction of Drain Level Control System (S1L)
l
Fan Motor (M1F) Lock, Overload
k
Malfunction of Swing Flap Motor (M1S)
l
Malfunction of Moving Part of Electronic Expansion Valve (Y1E)
k
Drain Level above Limit
l
Malfunction of Capacity Determination Device
l
Malfunction of Thermistor (R2T) for Heat Exchanger
l
Malfunction of Thermistor (R3T) for Gas Pipes
l
Malfunction of Thermistor (R1T) for Suction Air
k
Malfunction of Thermostat Sensor in Remote Controller
l
PCB Defect
l
Actuation of High Pressure Switch
l
Actuation of Low Pressure Sensor
l
Inverter Compressor Motor Lock
l
STD Compressor Motor Overcurrent/Lock
l
Malfunction of Outdoor Unit Fan Motor
l
Malfunction of Moving Part of Electronic Expansion Valve (Y1E, Y2E)
l
Abnormal Discharge Pipe Temperature
l
Refrigerant Overcharged
k
Failure of High Pressure Switch
l
Actuation of Low Pressure Switch
l
Abnormal Outdoor Fan Motor Signal
l
Malfunction of Thermistor (R1T) for Outdoor Air
l
Current Sensor Malfunction
l
Malfunction of Discharge Pipe Thermistor (R2T)
l
Malfunction of Thermistor (R3T, R5T) for Suction Pipe
l
Malfunction of Thermistor (R4T) for Outdoor Unit Heat Exchanger
l
Malfunction of Liquid Pipe Thermistor (R7T)
l
Malfunction of Subcooling Heat Exchanger Gas Pipe Thermistor (R6T)
l
Malfunction of High Pressure Sensor
l
Malfunction of Low Pressure Sensor
l
Inverter System Error
l
Malfunction of PCB
l
Malfunction of Inverter Radiating Fin Temperature Rise
l
Inverter Compressor Abnormal
l
Inverter Current Abnormal
l
Inverter Start up Error
l
Malfunction of Power Unit
l
Inverter Over-Ripple Protection
k
Malfunction of Inverter Radiating Fin Temperature Rise Sensor
Troubleshooting by Remote Controller
Malfunction contents
k : ON
h : OFF
l : Blink
Page
Referred
109
110
111
113
115
116
119
121
123
124
125
126
127
128
129
130
133
135
138
141
143
145
146
147
148
149
150
151
152
154
157
159
162
164
166
169
171
103