Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 83

60 hz.
Hide thumbs
Field Setting
Caution
DIP switch Setting after changing the main PCB(A1P) to spare parts PCB
When you change the main PCB(A1P) to spare parts PCB, please carry out the following setting.
Please Attach the Capacity Setting Adaptor corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adaptor
Position of Attaching the Capacity Setting Adaptor
X51A
Position of Attaching
the Capacity Setting Adaptor
74
Capacity Class
CAPACITY SETTING ADAPTOR (for 100/J112)
4 (112)
5 (140)
CAPACITY SETTING ADAPTOR (for 125/J140)
6 (160)
CAPACITY SETTING ADAPTOR (for 140/J160)
Note
SiUS34-907
Test Operation