Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 212

60 hz.
Hide thumbs
SiUS34-907
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting the connector, or parts may be damaged.
Did the
malfunction
occur while in the first test run
using the intelligent Touch
Controller?
YES
Is the
Master/Slave setting
of the centralized remote
controller correct?
NO
If the intelligent Touch Controller is
used, correct the setting of the
combination of master and slave units
again while in DIII-NET test run mode,
referring to the Master/Slave setting
table.
CHECK 10
: Refer to the information on P.219.
CHECK 10
Troubleshooting
Is the Master/
Slave setting of the
NO
centralized remote controller
correct?
YES
Was the
centralized remote
controller connected once, and
YES
then disconnected, or was
additional centralized
remote controller
installed?
NO
Turn ON the power supply of the
centralized remote controller with
MC
"
" displayed once again.
Is the "
displayed again?
NO
Troubleshooting (OP: Centralized Remote Controller)
NO
Be sure to
refer to the
Master/
Slave
setting
table.
CHECK 10
Correct the setting of the
combination of master and slave
units, and then reset the power
supplies of every centralized
remote controller.
YES
Reset the power supplies of
every centralized remote
controller.
MC
YES
"
Replace the centralized remote
controller.
centralized remote controller:
Normal
It is supposed that the
malfunction results from
external factors (e.g. noises)
from other equipment.
Reset the power supplies of
every centralized remote
controller.
203