Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 90

60 hz.
Hide thumbs
SiUS34-907
Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button, and confirm the data for
each setting.
 Data such as addresses and number of units is expressed as binary numbers; the two ways of expressing
are as follows:
l h l h l l h
16
32
8
l h h h l h l
No.12
128 32
l h h h l l h
No.13
8
 See the preceding page for a list of data, etc. for No. 0 - 25.
Test Operation
The No. 1 cool/heat unified address is expressed as a binary number consisting of
the lower 6 digits. (0 - 63)
4
1
2
In  the address is 010110 (binary number), which translates to 16 + 4 + 2 = 22
(base 10 number). In other words, the address is 22.
The number of terminal blocks for No. 12 and 13 is expressed as an 8-digit binary
number, which is the combination of four upper, and four lower digits for No. 12 and
64 16
13 respectively. (0 - 128)
In  the address for No. 12 is 0101, the address for No. 13 is 0110, and the
combination of the two is 01010110 (binary number), which translates to 64 + 16 + 4
4
1
+ 2 = 86 (base 10 number). In other words, the number of terminal block is 86.
2
Field Setting
81