L8" Outdoor Unit: Inverter Current Abnormal - Daikin VRV III-S RXYMQ6PV4A Service Manual

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
3.33 "L8 " Outdoor Unit:
L8
Remote
Controller
Display
Applicable
RXYMQ6P
Models
Method of
Malfunction is detected by current flowing in the power transistor.
Malfunction
Detection
Malfunction
When overload in the compressor is detected.
Decision
Conditions
Supposed
Causes
Troubleshooting
166
Inverter Current Abnormal
Compressor overload
Compressor coil disconnected
Defect of outdoor unit PC board (A1P)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Output current check
The
secondary
current of the inverter is
higher than 24.9A,
260 sec. for
each phase.
NO
Compressor
inspection The
compressor's coil is
disconnected.
NO
Disconnect the the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
Inverter
output
voltage check
Inverter output voltage
is not balanced
(Normal if within ±5V). Must
be measured when
frequency
is stable.
YES
After turning
on again, "L8" blinks
again.
YES
YES
YES
NO
NO
SiME34-608
Compressor overload
Inspection of the compressor and
refrigerant system is required.
Replace the compressor.
Replace outdoor unit PC board
(A1P).
Reset and restart.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
(V3184)