Daikin VRV III-S RXYMQ36 48PVJU Service Manual: Restart Standby; Stopping Operation

60 hz.
Hide thumbs
SiUS34-907
3.5

Restart Standby

Restart is stood by force to prevent frequent power-on/off and to equalize pressure in the refrigerant system.
Actuator
Compressor
Outdoor unit fan
Four-way valve (Y1S)
Main electronic expansion valve (EV1)
Subcooling electronic expansion valve
(EV3)
Hot gas bypass valve (SVP)
Ending conditions
3.6
Stopping Operation
Operation of the actuator when the system is down, is cleared up.
3.6.1 When System is in Stop Mode
Compressor
Outdoor unit fan
Four-way valve (Y1S)
Main electronic expansion valve (EV1)
Subcooling electronic expansion valve (EV3)
Hot gas bypass valve (SVP)
Ending conditions
Function
OFF
Ta>86°F: STEP 4
Ta≤86°F: OFF
Keep former condition.
0 pls
0 pls
OFF
2 min.
Actuator
Operation
OFF
OFF
Keep former condition.
0 pls
0 pls
OFF
Indoor unit thermostat is turned ON.
Special Control
Remarks
Operation
41