Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 175

60 hz.
Hide thumbs
Troubleshooting by Indication on the Remote Controller
L9
3.33 "
" Inverter Compressor Start up Error
L9
Remote
Controller
Display
Applicable
RXYMQ36 · 48PVJU
Models
Method of
Detect the failure based on the signal waveform of the compressor.
Malfunction
Detection
Malfunction
Starting the compressor does not complete.
Decision
Conditions
 Failure to open the stop valve
Supposed
 Defective compressor
Causes
 Wiring connection error to the compressor
 Large pressure difference before starting the compressor
 Defective main PCB
166
SiUS34-907
Troubleshooting