Page of 264
Download Table of ContentsContents Print This PagePrint Bookmark

Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 80

60 hz.
Hide thumbs
SiUS34-907
Group No. Setting Example
Indoor/Outdoor Outdoor/Outdoor
F1 F2
Caution
When turning the power supply on, the unit may often not accept any operation while "88" is displaying after all
indications were displayed once for about 1 minute on the liquid crystal display. This is not an operative fault.
3.1.8 Setting of Operation Control Mode from Remote Controller
(Local Setting)
The operation control mode is compatible with a variety of controls and operations by limiting the functions of the
operation remote controller. Furthermore, operations such as remote controller ON/OFF can be limited in
accordance with the combination conditions. (Refer to information in the next page.)
Centralized remote controller is normally available for operations. (Except when centralized monitor is
connected)
3.1.9 Contents of Control Modes
Twenty modes consisting of combinations of the following five operation modes with temperature and operation
mode setting by remote controller can be set and displayed by operation modes 0 through 19.
 ON/OFF control impossible by remote controller
Used when you want to turn on/off by centralized remote controller only.
(Cannot be turned on/off by remote controller.)
 OFF control only possible by remote controller
Used when you want to turn on by centralized remote controller only, and off by remote controller only.
 Centralized
Used when you want to turn on by centralized remote controller only, and turn on/off freely by remote
controller during set time.
 Individual
Used when you want to turn on/off by both centralized remote controller and remote controller.
 Timer operation possible by remote controller
Used when you want to turn on/off by remote controller during set time and you do not want to start operation
by centralized remote controller when time of system start is programmed.
Test Operation
F1 F2
F1 F2
P1 P2
F1 F2 P1 P2
RC
Main
1-00
F1 F2 P1 P2
F1 F2 P1 P2
No Remote Controller
1-03
Indoor/Outdoor Outdoor/Outdoor
F1 F2
F1 F2
F1 F2 P1 P2
RC
RC
RC
Sub
1-02
1-01
F1 F2 P1 P2
RC
1-04
Field Setting
Centralized Remote
Controller
F1 F2
F1 F2 P1 P2
Group Control by Remote Controller
(automatic unit address)
F1 F2 P1 P2
71

Advertising

This manual also for:

R-410a

Comments to this Manuals