Page of 264
Download Table of ContentsContents Print This PagePrint Bookmark

Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 152

60 hz.
Hide thumbs
SiUS34-907
F3
3.19 "
" Abnormal Discharge Pipe Temperature (R2T)
F3
Remote
Controller
Display
Applicable
RXYMQ36 · 48PVJU
Models
Method of
Abnormality is detected according to the temperature detected by the discharge pipe thermistor.
Malfunction
Detection
Malfunction
When the discharge pipe temperature rises to an abnormally high level (275 °F and above)
Decision
When the discharge pipe temperature rises suddenly (248 °F and above for 10 successive
minutes)
Conditions
 Faulty discharge pipe temperature
Supposed
 Faulty discharge pipe thermistor (R2T)
Causes
 Faulty outdoor unit PCB
Troubleshooting
Troubleshooting by Indication on the Remote Controller
143