Page of 264
Download Table of ContentsContents Print This PagePrint Bookmark

Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 19

60 hz.
Hide thumbs
Specifications
Slim Ceiling Mounted Duct Type
Model
1 Cooling Capacity
2 Heating Capacity
Casing / Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output
Fan
Airflow Rate (H/L)
External Static Pressure
4
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB (27°CDB), 67°FWB (19.4°CWB)
Outdoor temperature: 95°FDB (35°CDB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°CDB).
Outdoor temperature: 47°FDB (8.3°CDB), 43°FWB (6°FWB)
Equivalent ref. piping length: 25ft (7.5 m) (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure means
"High static pressure – Standard – Low static pressure".
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
10
FXDQ07MVJU
Btu/h
7,500
Btu/h
8,500
Galvanized Steel Plate
7-7/8 × 27-9/16 × 24-7/16
in. (mm)
(200 x 700 x 621)
2 × 12× 17
ft²(m²)
1.36 (0.41)
Sirocco Fan
HP
0.08
cfm
280/226 (H/L)
psi
0.0044-0.0015
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ1/4 (6.4) (Flare Connection)
in. (mm)
φ 1/2 (12.7) (Flare Connection)
in. (mm)
VP20
in. (mm)
(External Dia. 1-1/32 (26)
Internal Dia. 25/32) (20)
Lbs (kg)
51 (23)
dBA
33/29
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation for
Fitting, Sealing Pads, Clamps, Screws,
Washers, Conduit Mounting Plate,
Insulation Tube.
FXDQ09MVJU
9,500
10,500
Galvanized Steel Plate
7-7/8 × 27-9/16 × 24-7/16
(200 x 700 x 621)
2 × 12× 17
1.36 (0.41)
Sirocco Fan
0.08
280/226 (H/L)
0.0044-0.0015
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ1/4 (6.4) (Flare Connection)
φ 1/2 (12.7) (Flare Connection)
VP20
(External Dia. 1-1/32 (26)
Internal Dia. 25/32) (20)
51 (23)
33/29
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers, Conduit Mounting
Plate, Insulation Tube.
C:3D051780A
SiUS34-907
FXDQ12MVJU
12,000
13,500
Galvanized Steel Plate
7-7/8 × 27-9/16 × 24-7/16
(200 x 700 x 621)
3 × 12× 17
1.36 (0.41)
Sirocco Fan
0.08
280/226 (H/L)
0.0044-0.0015
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ1/4 (6.4) (Flare Connection)
φ 1/2 (12.7) (Flare Connection)
VP20
(External Dia. 1-1/32 (26)
Internal Dia. 25/32) (20)
51 (23)
33/29
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation for
Fitting, Sealing Pads, Clamps, Screws,
Washers, Conduit Mounting Plate,
Insulation Tube.