Page of 264
Download Table of ContentsContents Print This PagePrint Bookmark

Daikin VRV III-S RXYMQ36 48PVJU Service Manual Page 28

60 hz.
Hide thumbs
SiUS34-907
Concealed Floor Standing Type
Model
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output
Airflow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB (27°CDB), 67°FWB (19.4°CWB)
Outdoor temperature: 95°FDB (35°CDB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°CDB).
Outdoor temperature: 47°FDB (8.3°CDB), 43°FWB (6°FWB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Specifications
FXNQ12MVJU
Btu/h
12,000
Btu/h
13,500
Galvanized Steel Plate
24 × 42–1/8 × 8–5/8
in. (mm)
(610 x 1070 x 219)
3×14×17
ft² (m²)
2.15 (0.6)
2D14B13
Sirocco Fan
kw
0.03
cfm
280/210
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ1/4 (6.4)(Flare Connection)
in. (mm)
φ1/2 (12.7) (Flare Connection)
in. (mm)
φ27/32 (21.4) O.D (Vinyl Chloride)
in. (mm)
Lbs (kg)
56 (25)
dBA
36
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers, Level
Adjustment Screw.
FXNQ18MVJU
18,000
20,000
Galvanized Steel Plate
24 × 53–1/8 × 8–5/8
(610 x 1349 x 219)
3×14×17
3.04 (0.9)
2D14B20
Sirocco Fan
0.04
490/380
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ1/4 (6.4) (Flare Connection)
φ1/2 (12.7) (Flare Connection)
φ27/32 (21.4) O.D (Vinyl Chloride)
69 (31)
40
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Insulation for Fitting, Drain Hose,
Clamps, Screws, Washers, Level
Adjustment Screw.
3D045648
Specifications
FXNQ24MVJU
24,000
27,000
Galvanized Steel Plate
24 × 53–1/8 × 8–5/8
(610 x 1349 x 219)
3×14×17
3.04 (0.9)
2D14B20
Sirocco Fan
0.04
560/420
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber/ Urethane Foam
Resin Net (with Mold Resistant)
φ 3/8 (9.5) (Flare Connection)
φ 5/8 (15.8) (Flare Connection)
φ27/32 (21.4) O.D (Vinyl Chloride)
69 (31)
41
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.