Troubleshooting by Indication on the Remote Controller
L5
3.31 "
" Inverter Compressor Abnormal
L5
Remote
Controller
Display
Applicable
RXYMQ36 · 48PVJU
Models
Method of
Malfunction is detected from current flowing in the power transistor.
Malfunction
Detection
Malfunction
When an excessive current flows in the power transistor
Decision
(Instantaneous overcurrent also causes activation.)
Conditions
 Defect of compressor coil (disconnected, defective insulation)
Supposed
 Compressor start-up malfunction (mechanical lock)
Causes
 Defect of main PCB