60 hz.
Hide thumbs
SiUS34-907
E9
3.18 "
" Malfunction of Moving Part of Electronic Expansion
Valve (Y1E, Y3E)
E9
Remote
Controller
Display
Applicable
RXYMQ36 · 48PVJU
Models
Method of
Check disconnection of connector
To be detected based on continuity existence of coil of electronic expansion valve
Malfunction
Detection
Malfunction
No current is detected in the common (COM [+]) when power supply is ON.
Decision
Conditions
 Disconnection of connectors for electronic expansion valve (Y1E) or (Y3E)
Supposed
 Defect of moving part of electronic expansion valve
Causes
 Defect of outdoor unit main PCB (A1P)
Troubleshooting
Troubleshooting by Indication on the Remote Controller
141