Page of 264
Download Table of ContentsContents Print This PagePrint Bookmark

Daikin VRV III-S RXYMQ36 48PVJU Service Manual: Field Setting; Field Setting From Remote Controller

60 hz.
Hide thumbs
SiUS34-907

3. Field Setting

3.1
Field Setting from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of installation or after
service inspection / repair, make the local setting in accordance with the following description.
Wrong setting may cause malfunction.
When optional accessory is mounted on the indoor unit, setting for the indoor unit may be required to change.
Refer to information in the option handbook.
3.1.1 Wired Remote Controller <BRC1E71>
In the case of individual
setting per indoor unit
3
Field Settings
Unit No
4
0
0 –
01
5
4 –––
8 –––
Test Operation
<Basic screen>
1
Fan
Press and hold Cancel
button for 4 seconds or
more during backlight lit.
<Service Settings menu screen>
2
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential
Setting
Press Menu/OK button.
<Service Settings screen>
In the case of group total
3
Mode
5
20
1 – 01
2 – 02
3 – 01
5 –––
6 –––
7 –––
9 –––
a –––
b –––
Setting
FIRST CODE (SW) NO.
Press Menu/OK button.
1/3
setting
Field Settings
Unit No
Mode
0
10
0 –
1 –
2 –
3 –
01
4 –––
5 –––
6 –––
7 –––
8 –––
9 –––
a –––
b –––
Setting
SECOND CODE NO.
1
Press and hold Cancel button for
4 seconds or more.
Service settings menu is
displayed.
2
Select
Field Settings
in the
Service Settings menu, and
press Menu/OK button.
Field settings screen is dis-
played.
3
Highlight the mode, and select
desired "Mode No." by using
(Up/Down) button.
4
In the case of setting per indoor
unit during group control (When
Mode No. such as
20
,
22
,
23
,
25
are selected),
highlight the unit No. and select
"Indoor unit No." to be set by
using
(Up/Down) button.
(In the case of group total setting,
this operation is not needed.)
In the case of individual setting
per indoor unit, current settings
are displayed. And, SECOND
CODE NO. " - " means no
function.
5
Highlight SECOND CODE NO. of
the FIRST CODE NO. to be
changed, and select desired
"SECOND CODE NO." by using
(Up/Down) button. Multiple
identical mode number settings
are available.
In case of setting for all indoor
units in the remote control
group, available SECOND
CODE NO. is displayed as " ∗ "
which means it can be
changed.
When SECOND CODE NO. is
displayed as " - ", there is no
function.
Field Setting
21
,
59

   Related Manuals for Daikin VRV III-S RXYMQ36 48PVJU

This manual also for:

R-410a

Comments to this Manuals

Symbols: 0
Latest comments:
  • cp shukla Feb 16, 2016 06:50:
    RXYQ18PAY6 service manual & vrv Fulform