3.1.6 Detailed Explanation of Setting Modes

(1) Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Mode No.
10 (20)
(2) Ultra Long Life Filter Sign Setting
When a Ultra long
Mode No.
10 (20)
(3) Selection of Thermistor
Select the thermistor to control room temperature.
Mode No.
10 (20)
The factory setting for the Second Code No. is "01" and room temperature is controlled by the indoor unit suction
air thermistor and remote controller thermistor.
When the Second Code No. is set to "02", room temperature is controlled by the suction air thermistor.
When the Second Code No. is set to "03", room temperature is controlled by the remote controller thermistor.
(4) "Filter Cleaning" Displayed or Not Displayed
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
Mode No.
10 (20)
(5) Optional Output Switching
Using this setting, "operation output signal" and "abnormal output signal" can be provided. Output signal is output
between terminals K1 and K2 of "customized wiring adaptor", an optional accessory.
Mode No.
12 (22)
Test Operation
First Code
Second
No.
Code No.
01
0
02
life filter is installed, the filter sign timer setting must be changed.
-
First Code No.
1
First Code No.
2
First Code No.
3
First Code No.
0
Standard
Long Life
200 hrs.
2,500 hrs.
100 hrs.
1,250 hrs.
Second Code No.
01
02
Second Code No.
Thermistor that controls room temperature
Indoor air thermistor for remote controller and suction
01
air thermistor for indoor unit
02
Suction air thermistor for indoor unit
03
Thermistor for remote controller
Second Code No.
01
02
Second Code No.
01
Indoor unit thermostat ON/OFF signal is provided.
Output linked with "Start/Stop" of remote controller is
03
provided.
In case of "Malfunction Display" appears on the
04
remote controller, output is provided.
Ultra Long Life
Setting
10,000 hrs.
Contamination Light
5,000 hrs.
Contamination Heavy
Setting
Long-Life Filter
Ultra Long-Life Filter
"Filter Cleaning" display
Display
No display
Remarks
Field Setting