Parameter Reset - Honeywell VFD CORE Installation Instructions Manual

User and application manual
Hide thumbs Also See for VFD CORE:
Table of Contents

Advertisement

CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
00 - 02

Parameter Reset

Settings
• When it is set to 1, all parameters are read only except Pr.00-02~00-08 and it can be used with password setting for password
protection. It needs to set Pr.00-02 to 0 before changing other parameter settings.
• When it is set to 6: clear internal PLC program (includes the related settings of PLC internal CANopen master)
• When it is set to 7: reset the related settings of CANopen slave.
• When it is set to 9 or 10: all parameters are reset to factory settings. If the password is set in Pr.00-08, it needs to input the
password set in Pr.00-07 to reset to factory settings.
00 - 03
Start-up Display Selection
Settings
• This parameter determines the start-up display page after power is applied to the drive. User defined choice display according
to the setting in Pr.00-04.
00 - 04
Content of Multi-function Display (user defined)
~
Settings
63-4528—04
0: No Function
1: Write protection for parameters
6: Reset PLC (including CANopen Master Index)
7: Reset CANopen Index (Slave)
8: keypad lock
9: All parameters are reset to factory settings (base frequency is 50Hz)
0: Display the frequency command (F)
1: Display the actual output frequency (H)
2: Display User define (U)
3: Output current (A)
0: Display output current (A)
1: Display counter value (c)
2: Display actual output frequency (H.)
3: Display DC-BUS voltage (v)
4: Display output voltage (E)
5: Display output power angle (n)
6: Display output power in kW (P)
8: Display estimate output torque % (t = 00: positive torque; -00 negative torque) (t)
9: Display PG feedback (G) (refer to Note 1)
10: Display PID feedback in % (b)
11: Display AVI1 in % (1.), 0~10V/4-20mA/0-20mA corresponds to 0~100% (Refer to Note 2)
12: Display ACI in % (2.), 4~20mA/0~10V/0-20mA corresponds to 0~100% (Refer to Note 2)
13: Display AVI2 in % (3.), -10V~10V corresponds to -100~100% (Refer to Note 2)
14: Display the temperature of IGBT in
15: Display the temperature of capacitance in
o
C (i.)
o
C (c.)
124
Factory Setting: 0
Factory setting: 0
Factory setting: 0