CHAPTER 11: SUMMARIES OF PARAMETER SETTINGS
High-function PID Parameters
Parameter
08-00
08-01
08-02
08-03
Derivative Time (D)
08-04
08-05
08-06
Feedback Signal Detection
08-07
Time
08-08
Options on Feedback Error
08-09
Sleep Frequency
08-10
Wake-up Frequency
08-11
Sleep Time
08-12
PID Deviation Level
08-13
PID Deviation Time
08-14
Filter Time for PID Feedback
08-15
08-16
PID Compensation
08-17
08-18
Integral Limit during Wakeup
08-19
Enable PID to Change
08-20
Operating Direction
(PID Reserve)
63-4528-04
Table 9. High-function PID Parameters
Explanation
0: No function
1: Negative PID feedback: input from external terminal AVI1
(Pr.03-00)
4: Positive PID feedback from external terminal AVI1 (Pr.03-00)
0.0~500.0%
0.00~100.00 seconds
0.00~1.00seconds
0.0~100.0%
0.0~110.0%
0.0~35.0 seconds
0.0~3600.0 seconds
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
0.00~600.00Hz or 0~200.00%
0.00~600.00Hz or 0~200.00%
0.0~6000.0 seconds
1.0~50.0%
0.1~300.0 seconds
0.1~300.0 seconds
1: Analog input
-100.0~+100.0%
0: Follow PID output command
1: Follow PID feedback signal
0~200.0%
0: Operating direction cannot be changed
1: Operating direction can be changed
Settings
116
Factory
Setting
0
1.0
1.00
0.00
100.0
100.0
0.0
0.0
0
0.00
0.00
0.0
10.0
5.0
5.0
0
0
0
0

Advertisement