Communication parameter for VFD-CORE to connect to an Ethernet
Before VFD-CORE is linked to an Ethernet, set up the communication parameters shown in the table below. Then Ethernet
master will be able to read/write the frequency characters and control characters from/into VFD-CORE after communication
parameters are set.
CORE Parameters
00-20
00-21
09-30
09-75
09-76
09-77
09-78
09-79
09-80
09-81
09-82
09-83
09-84
09-85
09-86
09-87
Remove ETHERNET/IP COMMUNICATION CARD from VFD-CORE
1. Switch off the power supply of VFD-CORE.
2. Remove the two screws (see Figure 6).
3. Twist opens the card clip and inserts the slot type screwdriver to the hollow to prize the PCB off the card clip (see Figure 7).
4. Twist opens the other card clip to remove the PCB (see Figure 8).
[Figure 5]
Functions
Factory setting (Dec)
Set up source of
frequency command
Set up source of
operation command
Communication
decoding method
IP configuration
IP address-1
IP address-2
IP address-3
IP address-4
Net mask-1
Net mask-2
Net mask-3
Net mask-4
Default gateway-1
Default gateway-2
Default gateway-3
Default gateway-4
ETHERNET/IP COMMUNICATION CARD
[Figure 4]
M33575
0
Frequency command from keypad
Operation command from communication
5
card.
The decoding method for Honeywell VFD
0
(Honeywell AMD).
0
Static IP(0) / Dynamic IP
192
IP address 192.168.1.5
168
IP address 192.168.1.5
1
IP address 192.168.1.5
5
IP address 192.168.1.5
255
Net mask 255.255.255.0
255
Net mask 255.255.255.0
255
Net mask 255.255.255.0
0
Net mask 255.255.255.0
192
Default gateway 192.168.1.1
168
Default gateway 192.168.1.1
1
Default gateway 192.168.1.1
1
Default gateway 192.168.1.1
83
Explanation
63-4528—04