Honeywell VFD CORE Installation Instructions Manual page 193

User and application manual
Hide thumbs Also See for VFD CORE:
Table of Contents

Advertisement

06 - 63
Treatment for low current
Settings
06 - 64
Fire Mode
Settings
• This parameter needs to work with multi-input function terminal #58 or #59 and multi-output function terminal #53 and #54.
Setting is 0: Fire mode is disabled
Setting is 1: When there is a fire, motors will operate clockwise (U,V.W).
Setting is 2: When there is a fire, motors will operate counter-clockwise.
06 - 65
Operating Frequency when running Fire Mode (hz)
Settings
• This parameter is to set up the drive's frequency when the fire mode is enabled.
06 - 66
Enable Bypass on Fire Mode
Settings
06 - 67
Bypass Delay Time on Fire Mode
Settings
06 - 68
Auto-restart counter of Fire Mode
Settings
06 - 69
Length of Time to reset auto counter
Settings
• The settings of Pr06-66 to Pr06-69 decide if switch motors to operating under mains electricity.
0: No function
1: warn and coast to stop
2: warn and ramp to stop by 2
3: warn and operation continue
0: No Function
1: Forward Operation
2: Reverse Operation
0.00 ~ 600.00 hz
0: Disable Bypass
1: Enable Bypass
0.00 ~ 6550.0 seconds
0 ~ 10
0.00 ~ 6000.0sec
CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
nd
deceleration time
193
Factory Setting: 0
Factory Setting: 1
Factory Setting: 6000
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 0.00
63-4528—04