Honeywell VFD CORE Installation Instructions Manual page 93

User and application manual
Hide thumbs Also See for VFD CORE:
Table of Contents

Advertisement

Startup Wizard Guide
Follow the steps in the table below to complete the Startup Wizard.
Screen
Screen
#
Verbiage
1
Boot Screen Honeywell displayed for 3 seconds
2
Selection
Choose how to interact with the VFD:
Screen
Recommendation: Press function key F4 to start
the wizard
3
Select
Choose the keypad programming language
Language
Use UP and DOWN arrows to change from
default. Press ENTER to accept change.
F1 BACK up one menu (SAME function
throughout WIZARD)
F4 Next Parameter (SAME function throughout
WIZARD)
4
Clock Time
Select the time (Military) HH:MM:SS and date
and DATE
YY/MM/DD
5
Motor
Motor's rated voltage based upon Motor Name
Voltage
Plate data
6
Motor
Full Load AMPs (FLA)Do not use the motor
Current
service factor amperage for this value.
7
Motor FREQ Motor's rated frequency based upon Motor Name
Plate data
8
Motor RPM
Motor's rated RPM based upon Motor Name
Plate data
9
ACCEL
The time required to accelerate from the motor's
TIME
current speed reference to a new speed
reference
10
DECEL
The time required to decelerate from the motor's
TIME
current speed reference to a new speed
reference
11, 12,
PRESET
Present Speed options. On digital input closure
13
SPEED
the VFD will ignore the speed reference from the
1,2,3
analog input and will run at the programmed
speed.
14
Analog Input Select the speed reference signal type.
15
MIN
The minimum frequency at which the motor will
Frequency
operate
16
MAX
The maximum frequency at which the motor will
Frequency
operate
17
PRESS F4
Saves all parameter updates - VFD is ready to
to SAVE
operate
ALL
Table 3. Honeywell Commissioning Start-Up Wizard
Screen Description
N/A
F4: Initials the START UP WIZARD
Menu: redirects to MAIN MENU
ESC: redirects to MONITOR Screen
1. English (Default)
2. Spanish
3. Chinese
4. Portuguese
5. French
Use arrow keys to adjust. Press ENTER to save changes,
F4 to advance without changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
The default motor voltage is based on the VFD voltage that
you have selected
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
Acceleration time is factory set for typical Fan and Pump
needs. Use arrow keys to adjust. Press ENTER to save
changes, F4 to advance without changes.
Decceleration time is factory set for typical Fan and Pump
needs. Use arrow keys to adjust. Press ENTER to save
changes, F4 to advance without changes.
With the use of MFI (Multifunction inputs) 1, 2, or 3 the drive
can be sent to the programmed speed on digital input
closure (Usage not required in the field). Adjust as needed
or press F4 to accept factory defaults.
0. 0-10V - Use AVI (Analog Voltage Input terminal)
1. 4-20mA - Use ACI (Analog current input terminals)
2. 2-10V - Use AVI
3. 0-20mA - Use ACI
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
Press F4 to accept factory defaults. Use arrow keys to
adjust ONLY if needed. PRESS ENTER to save changes.
F1 will escape the user back to the Selection Screen again
F4 will save parameters and take the user to the display
screen
93
CHAPTER 10: DIGITAL KEYPAD
Screen options
63-4528—04