Honeywell VFD CORE Installation Instructions Manual page 223

User and application manual
Hide thumbs Also See for VFD CORE:
Table of Contents

Advertisement

09 - 28
CANopen Frequency Gain
Settings
09 - 29
CANopen Warning Record
Settings
09 - 30
CANopen Decoding Standard DS402
Settings
09 - 31
CANopen Status
Settings
09 - 32
CANopen Control Status
Settings
0.00 ~ 200
bit 0: CANopen Guarding Time out
bit 1: CANopen Heartbeat Time out
bit 2: CANopen SYNC Time out
bit 3: CANopen SDO Time out
bit 4: CANopen SDO buffer overflow
bit 5: Can Bus Off
bit 6: Error protocol of CANOPEN
0: Communication definition of CP2000 series
1: CANopen Standard DS402 protocol
0: Node Reset State
1: Com Reset State
2: Boot up State
3: Pre Operation State
4: Operation State
5: Stop State
0: Not ready for use state
1: Inhibit start state
2: Ready to switch on state
3: Switched on state
CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
223
Factory Setting: 100
Factory Setting: Read Only
Factory Setting: 1
Factory Setting: Read Only
Factory Setting: Read Only
63-4528—04