LED Indicators & Troubleshooting
LED Indicators
LED
Status
POWER
Green
LINK
Green
Flashes
Troubleshooting
Abnormality
POWER LED off
LINK LED off
No module found
Fail to open MODBUS
TCP/IP COMMUNICATION
CARD setup page
Able to open MODBUS
TCP/IP COMMUNICATION
CARD setup page but fail
to utilize webpage
monitoring
Fail to send e-mail
Indication
On
Power supply in normal status
Off
No power supply
On
Network connection in normal status
Network in operation
Off
Network not connected
Cause
VFD not powered
MODBUS TCP/IP
COMMUNICATION CARD not
connected to VFD
MODBUS TCP/IP
COMMUNICATION CARD not
connected to network
Poor contact to RJ-45 connector
MODBUS TCP/IP
COMMUNICATION CARD not
connected to network
PC and MODBUS TCP/IP
COMMUNICATION CARD in
different networks and blocked by
network firewall.
MODBUS TCP/IP
COMMUNICATION CARD not
connected to network
Incorrect communication setting in
DCISoft
PC and MODBUS TCP/IP
COMMUNICATION CARD in
different networks and blocked by
network firewall.
Incorrect network setting in
MODBUS TCP/IP
COMMUNICATION CARD
Incorrect network setting in
MODBUS TCP/IP
COMMUNICATION CARD
Incorrect mail server setting
CHAPTER 8: INSTALLATION OF THE OPTION CARDS
No action required
Check if the power supply is plugged.
No action required
No action required
Check if the network cable is connected
Check if VFD is powered, and if the power supply is
normal.
Make sure MODBUS TCP/IP COMMUNICATION CARD
is connected to VFD.
Make sure the network cable is correctly connected to
network.
Make sure RJ-45 connector is connected to Ethernet
port.
Make sure MODBUS TCP/IP COMMUNICATION CARD
is connected to network.
Search by IP or set up relevant settings by VFD keypad.
Make sure MODBUS TCP/IP COMMUNICATION CARD
is connected to the network.
Make sure the communication setting in DCISoft is set to
Ethernet.
Conduct the setup by VFD keypad.
Check if the network setting for MODBUS TCP/IP
COMMUNICATION CARD is correct. For the Intranet
setting in your company, please consult your IT staff. For
the Internet setting in your home, please refer to the
network setting instruction provided by your ISP.
Check if the network setting for MODBUS TCP/IP
COMMUNICATION CARD is correct.
Please confirm the IP address for SMTP-Server.
75
Action
Action
63-4528—04