01 - 28
Upper limit of Frequency 1 setting not allowed
01 - 29
Lower limit of Frequency 1 setting not allowed
01 - 30
Upper limit of Frequency 2 setting not allowed
01 - 31
Lower limit of Frequency 2 setting not allowed
01 - 32
Upper limit of Frequency 3 setting not allowed
01 – 33
Lower limit of Frequency 3 setting not allowed
Settings
• These parameters are used to set the skip frequency of the VFD. But the frequency output is continuous. There is no limit for
the setting of these six parameters and can be used as required.
• These parameters are used to set the skip frequency of the VFD. But the frequency output is continuous. The limit of these six
parameters is 01-28 ³ 01-29 ³ 01-30 ³ 01-31 ³ 01-32 ³ 01-33. This function will be invalid when setting to 0.0.
• The skip frequencies are useful when a motor has vibration at a specific frequency bandwidth. By skipping this frequency, the
vibration will be avoided. It offers 3 zones for use.
• The setting of frequency command (F) can be set within the range of skip frequencies. At this moment, the output frequency
(H) will be limited by these settings.
• When accelerating/decelerating, the output frequency will still pass the range of skip frequencies.
01 - 34
Zero-speed Mode
Settings
• When the frequency is less than Fmin (Pr.01-07 or Pr.01-41), it will operate by this parameter.
• When it is set to 0, the VFD will be in waiting mode without voltage output from terminals U/V/W.
• When it is set to 1, it will execute DC brake by Vmin(Pr.01-08 and Pr.01-42) in V/F and SVC modes.
• When it is set to 2, the VFD will run by Fmin (Pr.01-07, Pr.01-41) and Vmin (Pr.01-08, Pr.01-42) in V/F and SVC modes.
• In V/F and SVC modes
0.00~600.00Hz
01-28
01-29
INTERNAL
01-30
FREQUENCY
01-31
COMMAND
01-32
01-33
FREQUENCY SETTING COMMAND
0: Output waiting
1: Zero-speed operation
2: Output at Minimum Frequency (the 4th output
F OUT
01-34 0
STOP OUTPUT
F MIN
01-07
0 Hz
STOP WAITING
FOR OUTPUT
CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
M33617
01-34 1
01-34 2
0 Hz
0 Hz OPERATION
(DC BRAKE)
M33618
139
Factory Setting: 0.00
Factory Setting: 0