CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
09 Communication Parameters
09 - 00
COM1 Communication Address
Settings
• If the VFD is controlled by RS-485 serial communication, the communication address for this drive must be set via this
parameter. And the communication address for each VFD must be different and unique
09 - 01
COM1 Transmission Speed
Settings
• This parameter is used to set the transmission speed between the RS485 master (PLC, PC, etc.) and VFD.
09 - 02
COM1 Transmission Fault Treatment
Settings
• This parameter is set to how to react if transmission errors occur
09 - 03
COM1 Time-out Detection
Settings
• It is used to set the transmission time between communication and keypad.
09 - 04
COM1 Communication Protocol
Settings
63-4528—04
WHEN COMTROLLING
BY COMMUNICATION,
CONNECT THE DRIVE
AND PC BY IFD6530 OR
IFD6500 CONVERTER
1~254
4.8~115.2kbits/s
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
0.0~100.0 seconds
0.0: Disable
1: 7, N, 2 for ASCII
2: 7,E, 1 for ASCII
3: 7, O, 1 for ASCII
~
The parameter can be set during the operation.
SERIAL
6
1
COMMUNICATION
1: + EV
2: GND
3: SG –
4: SG +
5: NC
6: NC
RS-485
M33697
212
Factory Setting: 1
Factory Setting: 9.6
Factory Setting: 3
Factory Setting: 0.0
Factory Setting: 1