CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
01 Basic Parameter
01 - 00
Maximum Output Frequency
Settings
• This parameter determines the VFD's Maximum Output Frequency. All the VFD frequency command sources (analog inputs 0
to +10V, 4 to 20mA, 0 to 20mAand ±10V) are scaled to correspond to the output frequency range.
01 - 01
Motor1: Max Output Frequency (Hz) (Base Frequency/Motor Rated
Frequency)
Settings
01 - 02
Motor1: Max Output Voltage (V)
01 - 03
Mid-point Frequency 1 of Motor 1
Settings
Settings
01 - 04
Mid-point Voltage 1 of Motor 1
Settings
01 - 05
Mid-point Frequency 2 of Motor 1
Settings
01 - 06
Mid-point Voltage 2 of Motor 1
Settings
01 - 07
Min. Output Frequency of Motor 1
Settings
63-4528—04
~ The parameter can be set during operation.
50.00~600.00Hz
0.00~600.00Hz
230V series 0.0~255.0V
460V series 0.0~510.0V
0.00~600.00Hz
230V series 0.0~255.0V
460V series 0.0~510.0V
0.00~600.00Hz
230V series 0.0~240.0V
460V series 0.0~480.0V
0.00~600.00Hz
134
Factory Setting: 60.00/50.00
Factory Setting: 60.00
Factory Setting: 230.00/460.00
Factory Setting: 3.0
Factory Setting: 11.0/22.0
Factory Setting: 0.50
Factory Setting: 4.0/8.0
Factory Setting: 0.00