Honeywell VFD CORE Installation Instructions Manual page 153

User and application manual
Hide thumbs Also See for VFD CORE:
Table of Contents

Advertisement

02 - 31
Output Current Level Setting for Multi-function Output Terminals
Settings
• When output current is larger or equal to Pr.02-31, it will activate multi-function output terminal (Pr.02-13, 02-14, 02-16, and
02-17 is set to 27).
• When output current is smaller than Pr.02-31, it will activate multi-function output terminal (Pr.02-13, 02-14, 02-16, 02-17 is set
to 28).
02 - 32
Output Boundary for Multi-function Output Terminals
Settings
• When output frequency is higher than Pr.02-32, it will activate the multi-function terminal (Pr.02-13, 02-14, 02-16, 02-17 is set
to 29).
• When output frequency is lower than Pr.02-32, it will activate the multi-function terminal (Pr.02-13, 02-14, 02-16, 02-17 is set
to 30).
02 - 33
External Operation Control Selection after Reset and Activate
Settings
• Setting 1:
— Status 1: After the drive is powered on and the external terminal for RUN keeps ON, the drive will run.
— Status 2: After clearing fault once a fault is detected and the external terminal for RUN keeps ON, the drive can run after
pressing RESET key.
0~100%
0.00~±60.00Hz
0: Disable
1: Drive runs if the run command still exists after reset or re-boots.
CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
153
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 0
63-4528—04