Honeywell VFD CORE Installation Instructions Manual page 177

User and application manual
Hide thumbs Also See for VFD CORE:
Table of Contents

Advertisement

06 - 03
Over-current Stall Prevention during Operation
Settings
• It is a protection for drive to auto decrease output frequency when the motor is over-load abruptly during motor constant
operation.
• If the output current exceeds the setting specified in Pr.06-03 when the drive is operating, the drive will decrease its output
frequency (according to Pr.06-04) to prevent the motor stall. If the output current is lower than the setting specified in Pr.06-03,
the drive will accelerate (according to Pr.06-04) again to catch up with the set frequency command value.
OUTPUT
CURRENT
06-02
OVER-
CURRENT
DETECTION
LEVEL
OVER-CURRENT STALL
PREVENTION DURING
ACCELERATION,
FREQUENCY HELD
ORIGINAL SETTING OF
ACCELERATION TIME
ACTUAL ACCELERATION TIME WHEN OVER-
CURRENT STALL PREVENTION IS ENABLED
Heavy duty: 0~160%, 100% drive's rated current
Normal duty: 0~130%, 100% drive's rated current
OVER-CURRENT
DETECTION LEVEL
06-03
OVER-CURRENT STALL
PREVENTION DURING
OPERATION, OUTPUT
FREQUENCY DECREASES
DECREASES BY
DECELERATION TIME
OVER-CURRENT STALL PREVENTION DURING OPERATION
CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
SETTING
FREQUENCY
OUTPUT
FREQUENCY
M33667
CURRENT
PR. 06-03 SETTING
PR. 06-03 SETTING
RATED DRIVE
CURRENT x 5%
OUTPUT
FREQUENCY
TIME
M33668
177
TIME
Factory Setting: 120%
Factory Setting: 120%
63-4528—04