CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
• When setting Pr.00-10 to 2, the sensorless vector control diagram is shown as follows.
Fcmd
PR.00-14
00 - 11
Loading mode selection
Settings
• Normal duty 230V series & 460V series: When the output current is 110% of the rated output current, the endurance time is 60
seconds. When the output current is 130% of the rated output current, the endurance time is 3 seconds. Refer to Pr.00-12 for
the setting of carrier frequency. Refer to Pr.00-01 for the rated current.
• Heavy duty 230 V series & 460V series: When the output current is 120% of the rated output current, the endurance time is 60
seconds. When the output current is 160% of the rated output current, the endurance time is 3 seconds. Refer to Pr.00-12 for
the setting of carrier frequency. Refer to Pr.00-01 for the rated current.
00 - 12
Carrier Frequency
Settings
• This parameter determinates the PWM carrier frequency of the VFD.
63-4528—04
Fcmd
PR.00-14
ACCEL/DECEL TIME
DC BUS
VOLTAGE
DETECT
V/F
TABLE
01-00, 01-01
UPPER LIMIT F:01-10
01-02, 01-03
LOWER LIMIT F: 01-11
01-04, 01-05
01-06, 01-07
01-08
Vcmd
V/F
TABLE
ACCEL/DECEL
01-00, 01-01
TIME
01-02, 01-03
01-04, 01-05
01-06, 01-07
01-08
0: Normal duty
1: Heavy duty
2~15kHz
DC BUS VOLTAGE
IGBT
AVR
PWM
07-22
IRMS
DC BUS
VOLTAGE
DC BUS VOLTAGE
DETECT
AVR
07-22
UPPER LIMIT F:01-10
LOWER LIMIT F: 01-11
Fcmd
Factory Setting: As shown in table below
128
PROTECTION
CURRENT DETECTION
M
01-00
01-01
01-02
05-01
05-02
05-03
05-04
M33607
PROTECTION
CURRENT DETECTION
IGBT
M
PWM
01-00
01-01
01-02
05-01
05-02
05-03
05-04
IRMS
M33608
Factory Setting: 0