CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
00 - 21
User Defined Value
Settings
• Pr.00-21 will show user defined value when Pr.00-20 is not set to 0.
00 - 22
Local/Remote Selection
Settings
00 - 23
Source of the Master Frequency Command (HAND)
Settings
• It is used to set the source of the master frequency in HAND mode.
00 - 24
Source of the Operation Command (HAND)
Settings
• It is used to set the source of the operation frequency in HAND mode.
• Pr.00-14 and 00-15 are for the settings of frequency source and operation source in AUTO mode. Pr.00-23 and 00-24 are for
the settings of frequency source and operation source in HAND mode. The AUTO/HAND mode can be switched by the keypad
or multi-function input terminal (MI).
• The factory setting of frequency source or operation source is for AUTO mode. It will return to AUTO mode whenever power on
again after power off. If there is multi-function input terminal used to switch AUTO/HAND mode. The highest priority is the
multi-function input terminal. When the external terminal is OFF, the drive won't receive any operation signal and can't execute
JOG.
63-4528—04
Read Only
0: Standard HOA
1: LOC/REM not maintain
2: REM maintain
3: LOC maintain
4: LOC/REM maintain
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
6: CANopen communication card
8: Communication card (no CANopen card)
0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen communication card
5: Communication card (not including CANopen card)
132
Factory Setting: Read Only
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0