CHAPTER 11: SUMMARIES OF PARAMETER SETTINGS
Protection Parameters
Parameter
06-00
Low Voltage Level
Over-voltage Stall
06-01
Prevention
Over-current Stall
06-02
Prevention during
Acceleration
Over-current Stall
06-03
Prevention during
Operation
Accel. /Decel. Time
Selection of Stall
06-04
Prevention at Constant
Speed
Over-torque Detection
06-05
Selection (OT1)
Over-torque Detection
06-06
Level (OT1)
Over-torque Detection
06-07
Time (OT1)
Over-torque Detection
06-08
Selection (OT2)
Over-torque Detection
06-09
Level (OT2)
Over-torque Detection
06-10
Time (OT2)
06-11
Maximum Torque Limit
Electronic Thermal Relay
06-12
Selection (Motor 1)
Electronic Thermal
06-13
Characteristic for Motor 1
63-4528—04
Table 7. Protection Parameters
Explanation
230V: 160.0~220.0Vdc
460V: 320.0~440.0Vdc
230V: 350.0~450.0Vdc
460V: 700.0~900.0Vdc
Heavy duty: 0~160%(100%: drive's rated current);
Normal duty: 0~130%(100%: drive's rated current)
Normal Load: 0~160%(100%: drive's rated current);
Normal duty: 0~130%(100%: drive's rated current)
0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel
0: No function
1: Over-torque detection during constant speed operation,
continue to operate after detection
2: Over-torque detection during constant speed operation,
stop operation after detection
3: Over-torque detection during operation, continue to
operate after detection
4: Over-torque detection during operation, stop operation
after detection
10~200%, 100%: drive's rated current
0.0~60.0 seconds
0: No function
1: Over-torque detection during constant speed operation,
continue to operate after detection
2: Over-torque detection during constant speed operation,
stop operation after detection
3: Over-torque detection during operation, continue to
operation after detection
4: Over-torque detection during operation, stop operation
after detection
10~200%, 100%: drive's rated current
0.0~60.0 seconds
0~250% (100%: drive's rated current)
0: Motor with constant torque output
1: Motor with variable torque output
2: Electronic Thermal Relay disabled
30.0~600.0 seconds
Settings
110
Factory
Setting
180
360
380.0
760.0
Heavy duty:
120;
Normal duty:
120
Heavy duty:
120;
Normal duty:
120
0
0
120
0.1
0
120
0.1
170%
2
60.0