Honeywell VFD CORE Installation Instructions Manual page 70

User and application manual
Hide thumbs Also See for VFD CORE:
Table of Contents

Advertisement

CHAPTER 8: INSTALLATION OF THE OPTION CARDS
I/O Expansion Card
(6 Digital Inputs)
Relay Expansion Card
Screw Specifications for Option Cards' Terminals
I/O Extension Card
(4 Digital Input and 4 Digital Output)
I/O Extension Card
(6 Digital Input)
63-4528—04
Terminals
AC power Common for multi-function input terminal (Neutral)
AC
Refer to Pr. 02.26~ Pr. 02.31 in Chapter 11for multi-function input selection
Input voltage: 100~130VAC
Input frequency: 57~63Hz
MI9~ MI14
Input impedance: 27Kohm
Terminal response time:
ON: 10ms
OFF: 20ms
Terminals
Refer to Pr. 02.36~ Pr. 02.46 in Chapter 11 for multi-function output selection
Resistive load:
5A(N.O.)/3A(N.C.) 250VAC
5A(N.O.)/3A(N.C.) 30VDC
MO3 ~ MO13
Inductive load (COS 0.4)
2.0A(N.O.)/1.2A(N.C.) 250VAC
2.0A(N.O.)/1.2A(N.C.) 30VDC
It is used to output each monitor signal, such as drive is in operation, frequency
attained or overload indication.
Wire Gauge
Torque
Wire Gauge
Torque
Descriptions
Descriptions
24~12AWG (0.205~3.31mm
4Kg-cm [3.47Ib-in]
24~16AWG (0.205~1.31mm
6Kg-cm [5.21Ib-in]
70
2
)
2
)

Advertisement

Table of Contents
loading

Table of Contents