CHAPTER 6: CONTROL CIRCUIT TERMINAL
0-10V
AFM1
AFM2
0-20 mA
AFM1 +10V AVI1
AFM2 ACM AVI2 ACM
Control Terminal Specifications
Wire Gauge: 26~16AWG (0.1281-1.318mm
Screw Torque: (A) 5kg-cm [4.31Ib-in.] (0.49Nm) (As shown in Fig. 1 above.)
(B) 8kg-cm [6.94Ib-in.] (0.78Nm) (As shown in Fig. 1 above)
Wiring precautions:
• Reserve a bare wire strip of 5mm and properly install the wire into the terminal; tighten the installation with a slotted
screwdriver. If the wire is stripped, sort the wire before installation into the terminal.
• Use a flathead screwdriver: blade width 3.5mm, tip thickness 0.6mm
• In the Fig. 1 above, the factory setting for S1-SCM is short circuit. The factory setting for +24V-COM is short circuit and SINK
mode (NPN); please refer to Chapter 4 Wiring for more detail.
Terminals
Terminal Function
+24V
Digital control signal common (Source)
COM
Digital control signal common (Sink)
FWD
Forward-Stop command
REV
Reverse-Stop command
MI1
~
Multi-function input 1~8
MI8
DCM
Digital frequency signal common
63-4528—04
0-10V
0-10V
0-20 mA
AVI1
ACI
485
0-20 mA
0-20 mA
0-10V
ACI DCM +24V +24V COM FWD MI1
DCM REV
MI2
S1
SCM
Fig. 1. Removable terminal block.
2
)
Table 1. Control terminal specifications.
Open
RC3 RA3 RC2 RA2 RC1 RB1
120
MI3
MI5
MI7
MI4
MI6
MI8
SG+
SG-
Factory Setting (NPN mode)
+24V±5% 200mA
Common for multi-function input terminals
FWD-DCM:
ON
forward running
OFF
deceleration to stop
REV-DCM:
ON
reverse running
OFF
deceleration to stop
Refer to parameters 02-01~02-08 to program the multi-function inputs
MI1~MI8.
ON: the activation current is 6.5mA 11Vdc
OFF: leakage current tolerance is 10μA 11Vdc
30
A
RA1
B
M33261