Honeywell VFD CORE Installation Instructions Manual page 220

User and application manual
Hide thumbs Also See for VFD CORE:
Table of Contents

Advertisement

CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
4. Exception response:
The VFD is expected to return a normal response after receiving command messages from the master device. The following
depicts the conditions when no normal response is replied to the master device.
The VFD does not receive the messages due to a communication error; thus, the VFD has no response. The master device will
eventually process a timeout condition.
The VFD receives the messages without a communication error, but cannot handle them. An exception response will be returned
to the master device and an error message "CExx" will be displayed on the keypad of VFD. The xx of "CExx" is a decimal code
equal to the exception code that is described below.
In the exception response, the most significant bit of the original command code is set to 1, and an exception code which explains
the condition that caused the exception is returned.
63-4528—04
2107H
Current step number of Multi-Step Speed Operation
2109H
Counter value
2116H
Multi-function display (Pr.00-04)
211BH
Max. setting frequency
2200H
Display output current (A)
2201H
Display counter value of TRG terminal (c)
2202H
Display actual output frequency (H)
2203H
Display DC-BUS voltage (u)
2204H
Display output voltage of U, V, W (E)
2205H
Display output power angle of U, V, W (n)
2206H
Display actual motor speed kW of U, V, W (P)
2207H
Display motor speed in rpm estimated by the drive or encoder feedback (r00:
positive speed, -00: negative speed)
2208H
Display positive/negative output torque N-m estimated by the drive (t0.0:
positive torque, -0.0: negative torque)
2209H
Display PG feedback (as NOTE 1)
220AH
Display PID feedback value after enabling PID function in % (b)
220BH
Display signal of AVI1 analog input terminal, 0-10V corresponds to 0-100%
(1.) (as NOTE 2)
220CH
Display signal of ACI analog input terminal, 4-V20mA/0-10V corresponds to
0-100% (2.) (as NOTE 2)
220DH
Display signal of AVI2 analog input terminal, -10V~10V corresponds to -
100~100% (3.) (as NOTE 2)
220EH
Display the IGBT temperature of drive power module in
220FH
Display the temperature of capacitance in
2210H
The status of digital input (ON/OFF), refer to Pr.02-10 (as NOTE 3)
2211H
The status of digital output (ON/OFF), refer to Pr.02-15 (as NOTE 4)
2212H
Display the multi-step speed that is executing (S)
2213H
The corresponding CPU pin status of digital input (d.) (as NOTE 3)
2214H
The corresponding CPU pin status of digital output (O.) (as NOTE 4)
2215H
Reserved
2216H
Reserved
2217H
Reserved
2218H
Reserved
2219H
Display times of counter overload (0.)
221AH
Display GFF in % (G.)
221BH
Reserved
221CH
Display PLC register D1043 data (C)
221DH
Reserved
221EH
User page displays the value in physical measure
221FH
Output Value of Pr.00-05
220
o
C (c.)
o
C (i.)

Advertisement

Table of Contents
loading

Table of Contents