CHAPTER 5: MAIN CIRCUIT TERMINAL
FRAME C
FRAME D
63-4528-04
Main Circuit Terminals:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
Model
HCRDA0250C1000T
HCRDA0300C1000T
HCRDA0400C1000T
HCRDC0300C1000T
HCRDC0400C1000T
HCRDC0500C1000T
NOTE: UL installations must use 600V, 75
Terminal D+ [+2 & +1]:
Torque: 90 Kg-cm [78.2 lb-in.] (8.83Nm) (±10%)
use 600V, 90
ambient temperature exceeds 40
M33255
Main Circuit Terminals:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
Model
HCRDA0500D1000T
HCRDA0600D1000T
HCRDC0600D1000T
HCRDC0750D1000T
HCRDC1000D1000T
HCRDC1250D1000T
1.
UL installations must use 600V, 75
only.
HCRDC0600D1000T and HCRDC1250D1000T must use 90
2.
Figure on the left (below) shows the terminal specification.
3.
Figure on the right (below) shows the specifications of insulated heat
shrink tubing that comply with UL (600C, YDPU2).
4.
Specification of ground wire
as the Min. Wire Gauge listed above.
M33256
, B1, B2, +1, +2, -
Max. Wire
Gauge
1/0 AWG
2
(53.5mm
)
1/0 AWG (53.5mm
1/0 AWG (53.5mm
o
C wired for UL installation for HCRDA0400C1000T install in
o
+1/DC+, -/DC-
Max. Wire
Gauge
4/0 AWG
4/0 AWG (107mm
2
(107mm
)
4/0 AWG (107mm
1/0 AWG (53.5mm
2/0 AWG (67.4mm
4/0 AWG (107mm
4/0 AWG (107mm
RING LUG
28 MAX.
RING
LUG
28 MAX.
26
Min. Wire Gauge
Torque (±10%)
2
M8 80kg-cm
1 AWG (42.4mm
)
(69.4 lb-in.)
2
)
(7.848Nm)
2
)
2
4 AWG (21.2mm
)
2
4 AWG (21.2mm
)
2
2 AWG (33.6mm
)
o
o
C or 90
C wire. Use copper wire only.
C.
Min. Wire Gauge
Torque (±10%)
2
M8 200kg-cm
)
(173 lb-in.)
2
)
(19.62Nm)
2
)
2
)
2
)
2
)
o
o
C or 90
C wire. Use copper wire
: It needs to be at least the same size
HEAT
SHRINK
TUBE
WIRE
M31492
o
C wire.