CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
05 - 02
Rated Power of Induction Motor 1(kW)
Settings
• It is used to set rated power of the motor 1. The factory setting is the power of the drive
05 - 03
Rated Speed of Induction Motor 1 (rpm)
Settings
• It is used to set the rated speed of the motor and need to set according to the value indicated on the motor nameplate.
05 - 04
Pole Number of Induction Motor 1
Settings
• It is used to set the number of motor poles (must be an even number).
05 - 05
No-load Current of Induction Motor 1 (A)
Settings
• Factory setting is 40% of the drive's rated current.
Settings
• It is used to set the rated speed of the motor and need to set according to the value indicated on the motor nameplate.
05 - 06
Accumulative Motor Operation Time (Min)
Settings
05 - 07
Accumulative Motor Operation Time (Day)
Settings
• Pr. 05-06 and Pr.05-07 are used to record the motor operation time. They can be cleared by setting to 00 and time won't be
recorded when it is less than 60 seconds
63-4528—04
0~655.35 kW
0~65535
2~20
0 to the factory setting in Pr.05-01
0~65535
0~1439
00~1440
174
Factory Setting: 0
Factory Setting:
1710: 60Hz 4 poles
1410: 50Hz 4 poles
Factory Setting: 4
Unit: Ampere
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0