Operating Guide | VLT® Midi Drive FC 280
Restoring Default Settings with LCP
5.4.10
5.4.10.1
Introduction
BACK UP DATA TO LCP
Risk of losing programming, motor data, localization, and monitoring records by restoration of default settings.
To provide a backup, upload data to the LCP before initialization.
l
Restoring the default parameter settings is done by initialization of the drive. Initialization is carried out via parameter 14-22 Operation
Mode (recommended) or manually.
Recommended initialization via parameter 14-22 Operation Mode does not reset the following settings:
Operating hours.
l
Serial communication selections.
l
Fault log.
l
Alarm log.
l
Other monitoring functions.
l
Parameter 0-03 Regional Settings.
l
Parameter 1-06 Clockwise Direction.
l
Manual initialization erases all motor, programming, localization, monitoring data, and restores factory default settings. Manual
initialization does not reset the following information:
Parameter 0-03 Regional Setting.
l
Parameter 1-06 Clockwise Direction.
l
Parameter 15-00 Operating hours.
l
Parameter 15-03 Power Up's.
l
Parameter 15-04 Over Temp's.
l
Parameter 15-05 Over Volt's.
l
Recommended Initialization
5.4.10.2
1.
Select parameter 14-22 Operation Mode and press [OK].
2.
Select [2] Initialisation and press [OK].
3.
Remove power to the unit and wait until the display turns off.
4.
Apply power to the unit. Default parameter settings are restored during start-up. This may take slightly longer than normal.
5.
Alarm 80, Drive initialised to default value is shown.
6.
Press [Reset] to return to operating mode.
Manual Initialization
5.4.10.3
1.
Remove power to the unit and wait until the display turns off.
2.
Press and hold [Status], [Main Menu], and [OK] at the same time on the GLCP, or press [Menu] and [OK] at the same time on the
NLCP while applying power to the unit (approximately 5 s or until a click is heard and the fan starts).
3.
Factory default parameter settings are restored during start-up. This may take slightly longer than normal.