Download Print this page

Danfoss VLT FC 280 Operating Manual page 54

Midi drive with profisafe
Hide thumbs Also See for VLT FC 280:

Advertisement

Operating Guide | VLT® Midi Drive FC 280
PUD file.
l
SIVP file.
l
Parameter file.
l
The VLT® Memory Module MCM is an accessory. The drive comes without the memory module installed from the factory. A new memory
module can be ordered using the following ordering numbers.
Table 19: Code Number
Description
VLT® Memory Module MCM 102
VLT® Memory Module MCM 103
Each memory module has a unique serial number which cannot be modified.
The VLT® Memory Module MCM can be used on the drive together with firmware 1.5 and above.
The VLT® Memory Module MCM does not support copying functional safety-related firmware and parameters.
Select correct options for parameter 31-40 Memory Module Function before configuring with the memory module.
Table 20: Description of Parameter 31-40 Memory Module Function
Parameter 31-40 Memory Module Function
[0] Disabled
*[1] Only Allow Download
[2] Only Allow Upload
[3] Allow Both Download and Upload
AVOID UNINTENTIONAL OVERWRITING
The default setting of parameter 31-40 Memory Module Function is [1] Only Allow Download. If there is any update, such as
firmware updated by MCT 10 using OSS file, parameter updated by LCP or bus, parameters reset via parameter 14-22 Operation
Mode, or 3-finger-reset of the drive, the updated data will be lost after a new power cycle, because the drive downloads data from
the memory module again.
After the data has been downloaded from the memory module to the drive, select [0] Disabled or [2] Only Allow Upload in
l
parameter 31-40 Memory Module Function before the new power cycle.
5.10.2
Synchronizing Drive Data to a New Memory Module (Create Drive Backup)
Prerequisite:
54
| Danfoss A/S © 2024.10
Code number
132B0359
132B0466
  NOTICE
  NOTICE
Description
Downloading or uploading data function is disabled.
Only allow downloading data from the memory module to the drive. This is the
default setting of parameter 31-40 Memory Module Function.
Only allow uploading data from the drive to the memory module.
If this option is selected, the drive downloads data from memory module first,
and then uploads data from the drive to the memory module.
  NOTICE
Commissioning
AQ381425076031en-000201 / 130R1223

Advertisement

loading
Need help?

Need help?

Do you have a question about the VLT FC 280 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Midi drive fc 280