Download Print this page

Danfoss VLT FC 280 Operating Manual page 25

Midi drive with profisafe
Hide thumbs Also See for VLT FC 280:

Advertisement

Operating Guide | VLT® Midi Drive FC 280
For EMC-compliant installation
Establish electrical contact between the cable shield and the drive enclosure by using metal cable glands or by using the clamps
l
provided on the equipment.
Use high-strand wire to reduce burst transient.
l
Do not use pigtails.
l
POTENTIAL EQUALIZATION
Risk of burst transient when the ground potential between the drive and the control system is different. Install equalizing cables
between the system components. Recommended cable cross-section: 16 mm
Danfoss A/S © 2024.10
  NOTICE
2
(6 AWG).
Electrical Installation
AQ381425076031en-000201 / 130R1223 |
25

Advertisement

loading
Need help?

Need help?

Do you have a question about the VLT FC 280 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Midi drive fc 280