For more information, read the description of parameter 42-31 Reset Source.
The default restart behavior is set to Manual. Before switching to Automatic, ensure to follow the requirements of the integrator
risk assessment.
Commissioning and Validation
6.9
Safety Guidelines
6.9.1
Always perform a commissioning test after installation, maintenance, retrofit, and reconfiguration.
When commissioning/recommissioning:
Secure the site in accordance with regulations (barrier, warnings, signs, and so on).
l
Only qualified personnel are allowed to commission/recommission the system.
l
Refer to the guidelines, information, and specifications stated in the operating guides of relevant programmable control systems.
l
Make sure that no personal injury and/or material damage can occur, even if the plant/machine moves unintentionally.
l
ELECTROSTATIC DISCHARGE
Electrostatic discharge can damage components.
Ensure discharge before touching the safety option, for example, by touching a grounded, conductive
l
surface or by wearing a grounded armband.
RISK OF ELECTROCUTION
Never wire the electrical connections on the drive while voltage is applied.
l
Switch off power.
l
Make sure that the control cabinet is provided with access lock or warning signs.
l
DO NOT switch on the voltages until the system is commissioned.
l
Refer to other chapters of this operating guide for further information of the drive. Refer to VLT® Motion Control Tool MCT 10 Operating
Guide for further information on the Safe Plug-in.
6.9.2

Commissioning Requirements

The procedure requires installation of MCT 10 setup software, version 5.80 or later, and a successful connection to VLT® Midi Drive FC 280
with built-in safety option.
Configure the safety option in the MCT 10 with safe plug-in. Ensure only to configure safety functions that are wired up to the safety
l
option inputs.
Ensure that the device number (serial number and order number) of the safety option on the drive matches the device number of
l
the safety option in the MCT 10 safe plug-in.
Ensure that the drive is ready for commissioning.
l
The following components are required to perform the necessary steps for commissioning the safety option.
VLT® Motion Control Tool MCT 10 set-up software (licensed version).
l
Danfoss A/S © 2024.10
  NOTICE
  NOTICE
  CAUTION
  WARNING
Safety Functions
AQ381425076031en-000201 / 130R1223 |
95

Advertisement

loading
Need help?

Need help?

Do you have a question about the VLT FC 280 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Midi drive fc 280