CHAPTER 2 PREPARATIONS

2.3 Wiring Terminals

J Terminal arrangement
J Precautions
when wiring
J Wiring
F Power supply
10
20
21 22
9
19
8
18
7
17
6
16
5
15
4
14
3
13
2
12
23
1
11
2--8
10
SOURCE
9
8
OUT1
7
6
OUT2
5
4
SUB1
3
2
SUB2
1
TRSF
: Transfer output
EV1/2
: Event inputs
PTMR
: Potentiometer
SOURCE : 100 to 240 VAC, 50/60 Hz 15VA or 24VAC/DC, 50/60 Hz, 12VA 8W
• On some models, terminals are not used and are left free. Do not wire
these terminals.
• Separate input leads and power lines in order to protect the controller
and its lines from external noise.
• We recommend using solderless terminals when wiring the controller.
• Tighten the terminal screws using a torque no greater than 0.78 N¡m
(8kgf¡cm).
• Use the following type of solderless terminals for M3.5 screws.
In the following wiring diagrams, the left side of the terminal Nos. indi-
cates the inside of the controller.
• Input power to terminals Nos. 9 and 10. Power specifications are as fol-
lows:
100 to 240 VAC, 50/60 Hz, approx. 15 VA
or
24 VAC, 50/60 Hz, approx. 12 VA
24 VDC, 8W
EV1/2
TRSF
20
RS232C
21 22
RS422
19
RS485
18
17
CT
16
PTMR
15
14
TC
13
Pt
I
12
V
23
11
7.2mm max.
7.2mm max.