CHAPTER 5 PARAMETERS
Level 1 Mode
Control period (heat)
Control period (cool)
• Sets the pulse output period. Set the control period taking the control characteris-
tics and life expectancy of the controller into consideration.
• In a standard control system, use the "control period (heat)" parameter. The "con-
Function
trol period (cool)" parameter cannot be used.
• In a heating and cooling control system, the control period can be set indepen-
dently for heating and cooling. Use the "control period (heat)" parameter to set
the heating side control period, and use the "control period (cool)" parameter to
set the cooling side control period.
Setting
F Related description
3.3 Setting Output Specifications (page 3-7)
F Related parameters
See
"Control output 1 assignment" "Control output 2 assignment" (setup mode)
E5EK-TAA2
Model
5--22
Parameter
Setting Range
Control period (heat)
Control period (cool)
Conditions of Use
Relay, SSR or voltage output must set
as the outputs, and the control must be
set to advanced PID control, standard
control or heating and cooling control.
Unit
1 to 99
Second
1 to 99
Second
Default
20
20