CHAPTER 4 APPLIED OPERATION
4.5 Wait Operation
Parameters
4--16
• "Wait" is the operation of not advancing the program steps and wait-
ing for the PV to enter the preset wait width at the end of each step.
During wait operation, the "WAIT" LED lights.
SP
PV
During wait
Counting stop
• As the PV is smaller than "SP - wait width" at the end of the rising
step in the above figure, control monitoring is stopped, and the con-
trol waits for PV to reach "SP - wait width" before the step is up-
dated.
• In the case of a falling step, the control waits for PV to reach "SP +
wait width."
• Set the wait width in the "wait width" parameter (expansion mode)
within the range 0 to 9999 (EU). (Default is "0".)
• Setting the "wait width" to "0" disables wait operation.
Symbol
Parameter Name: Mode
Wait width
Wait width
Wait width
Step updated
Time
Description
: Expansion
Wait operation